Main Features:
- Multiparameter monitoring.
- All parameters with default accuracy class 1.0.
- Measures V, I, KW and Hz.
- All parameters with default accuracy class
- Compact 96 x 96 x 55 mm DIN enclosure.
- Micro-controller based.
- True RMS.
Note : Options available on request
- Tiny Pro 3 (PF,KW and KWH),
- Tiny Pro 4 (V,I,Hz, and KWH)
- Tiny Pro 5 (V,I,Hz,KW and KWH),
- Tiny Pro 6 (V,I,PF,Hz,KW and KWH),
|
Sr.
No. |
Parameters
& Options |
Statistics |
| 01 |
Volts R-N |
Direct Voltage Input : Up to 300V L-N
Burden : 0.5VA
Secondary Voltage Input : 63.5V* |
| 02 |
Volts Y-N
|
| 03 |
Volts B-N |
| 04 |
Volts RY |
Direct Voltage Input : Up to 500V L-L
Burden : 0.5VA
Secondary Voltage Input : 110V* |
| 05 |
Volts YB |
| 06 |
Volts BR |
| 07 |
Current R |
Secondary Current Input : 5A or 1A (To be specified
at the
time of Ordering)
CT Primary : Site Selectable
Range of Reading : 0 – 4000A
Burden : < 1.0VA
Overload(Through CT) : 5A CT = 6A RMS Continuous
1A CT = 1.2A RMS Continuous
(Whole Current) : 120% of Imax continuous. |
| 08 |
Current Y |
| 09 |
Current B |
| 10 |
Frequency |
45 to 55 Hz, Accuracy : 0.3% of Reading |
| 11 |
KWh |
Range of Reading : 0 to 9999999.9 KWh
Accuracy : 1.0S as per IS13779. |
| 12 |
KVARh |
Range of Reading : 0 to 9999999.9 KWh
Accuracy : 1.5% of Reading
(Between 0.5 Lag to 0.8 Lead) |
| 13 |
KVAh |
Range of Reading : 0 to 9999999.9 KWh
Accuracy : 1.0% of Reading |
| 14 |
System PF |
Accuracy : 1% of Reading (IPFI>0.5)
Range of Reading : 0.05 to 1.00 Lag/Lead
|
| 15 |
System KVA |
Accuracy : 1.0% of Reading |
| 16 |
System KW |
Accuracy : 1.0% of Reading
(Between 0.5 Lag to 0.8 Lead) |
| 17 |
System KVAR |
Accuracy : 1.5% of Reading
(Between 0.5 Lag to 0.8 Lead) |
| 18 |
DISPLAY |
0.4” Red Seven Segment. |
| 19 |
RS485 |
For Integration with EMS/SCADA |
| 20 |
Bezel |
96x96 mm |
DIN enclosure |
| 21 |
Depth |
55 mm |
|