Trinity has designed its Portable Power Analyzers, R2D2 to be the most versatile! Single Phase Power Analyzer and Recorder! available today. This next generation analyzer has important new features requested by our customers including LCD Display; USB Download & Motor mode for Three Phase balanced motor loads. From commercial & industrial, to residential monitoring, R2D2 has wide-ranging measurement and power quality analysis capabilities. These high performance capabilities, combined with the latest in electronic technology, make it ideal for both utility and industrial applications.




  • A rugged full-featured instrument measuring all essential power quality data including Harmonics & Demands.
  • Measures voltage, current, imbalance, power, energy, events, THD, individual harmonics, and frequency.
  • Real-time, graphical display of harmonic content upto 15th.
  • Integrated analysis and data retrieval capabilities of 8 MB in Oracle and 32 KB in R2D2 by USB port.

  • Features
  • Specifications

Accessories

1) Clamp-on CTs with Below Specification:

Ordering Information : Model, CT Ratio, Single / Triple Range, Colour

Model S
Transformer ratio
(Arms) 
600/300mA, 5A/2mA
(Single Range)
  1A, 5A, 300mA
(Triple Range)
Overload (Arms)     120% continuous, 200%
for 5 min/ h
Weight 610 gm approx.
Colours   Red, Yellow, Blue
Dimensions  Overall 215(L) x 101(W)
x 40(D) mm.
5000 Hz  53 mm max.
Conductor size   ¯ 53 mm.
Bus bar    51 x 12mm
Connections  : Safety sockets for banana
plugs ¯ 4mm
Accuracy class 2 1 0.5
Rated burden 0.8 W    
Frequency range 30Hz to
5000 Hz
45 Hz to
1000Hz
50 Hz to
400 Hz

Note

Clamps with specifications other than above available subject to technical specifications.

Technical Specifications

  Parameter Statistics
Type Name   ORACLE R2D2
True RMS
Basic Parameters
Voltage
(Volts L-N)
Direct Voltage Input 0 to 300V AC
PT Ratio Freely Programmable up to 220KV Freely Programmable up to 66KV
Range of Reading 0.0 to 220KV 0.0 to 66KV
Accuracy 0.5% of Reading
Voltage
(Volts L-L)
Direct Voltage Input 0 to 51 0V AC
PT Ratio Freely Programmable up to 220KV Freely Programmable up to 66KV
Range of Reading 0.0 to 220KV 0. 0 to 66KV
Accuracy 1.0% of Reading
Current
(Amps Ir, Iy, Ib)
Secondary Current Input 2mA, 300mA, 1000mA
CT Ratio Freely Programmable up to 9999A Freely Programmable up to 999A
Range of Reading 0.0 to 9999A 0.0 to 999A
Accuracy 0.25% of Reading
Neutral Current Accuracy 3% of Reading N/A
Line Frequency Range of Reading 45 to 55 Hz
Accuracy 0.3% of Reading
Power Active Power (P) Accuracy (Between 0.5 Lag to 0.8 Lead) 1.0% of Reading
Reactive Power (Q) Accuracy (Between 0.5 Lag to 0.8 Lead) 1.5% of Reading
Apparent Power (S) Accuracy 1.0% of Reading
Power Factor Accuracy 1% of Reading (IPFI>0.5)
Range of Reading 0.05 to 1.00 Lag/Lead
Energy Total Active Energy (KWh) Range of Reading 0 to 314780.00 MWh
Accuracy 1.0S as per IS13779
Total Reactive Energy
(KVARh)
Range of Reading 0 to 314780.00 MWh
Accuracy(Between 0.5 Lag to
0.8 Lead)
1.5% of Reading
Total Apparent Energy
KVAh)
Range of Reading 0 to 314780.00 MWh
Accuracy 1.0% of Reading
Demand Active Power (KW) Demand Sliding & Fixed Selectable N/A
Apparent Power (KVA) Demand
Predictive Demand Fixed Window N/A
Power Quality Harmonics for Voltages 3rd to 29th Odd Only 3rd to 15th Odd Only
Harmonics for Currents 3rd to 29th Odd Only 3rd to 15th Odd Only
THD for each Voltage
THD for each Current
Misc. Phase angles N/A
Run time N/A

Input Specifications

Supply

ORACLE : Three Phases and Neutral of a 3P4W system / Three phases of a 3P3W system.

R2D2 : One Phase and Neutral of a 1P2W system.

  ORACLE R2D2
Voltage:  
Direct Voltage Input Up to 510V L-L and 300V L-N
PT Ratio Freely Programmable up to 220KV Site selectable. Freely Programmable up to 66KV Site selectable.
Range of Reading 1-220KV 1-66KV
Burden 0.5VA
Current:  
Secondary Current Input 5A or 1A
Range of Reading 0 - 9999A 0 - 999A
Burden < 1.0VA
Overload 5A CT = 6A RMS Continuous 1A CT = 5A RMS Continuous

Power Supply

Oracle : Self Power. Unit has in-built 3 phase supply with an operating range of 60 VAC - 480 VAC, 50-60 Hz. Mains supply (80-500 VAC) for connection at lab/office while downloadable data.

R2D2 : There are two entirely new sources of power. A small SMPS derives power from the line itself when connected to the electrical system, and powers the system. No need for adapter/battery. During downloading process, since the unit connects to the PC/Laptop through USB cable, it derives power straight from USB port itself.


Data Logging

Produrt Records Logging Interval Total Duration
Min. Max.
Oracle 30395 1 Sec. 16.65 Min (999Sec.) 8.4 Hours 351.4
R2D2 1025 02 Sec. to 16.65 Min (999Sec.) 1 Hours 12 Days

Display: 320 X 240 Color TFT (In Oracle)
20 X 4 Line Graphics LCD (B/W), with LED backlight (In R2D2).
Dimensions: ORACLE : 225(W) X 198(H) X 80(D) mm.
R2D2: 110(W) X 220(H) X 45(D) mm.
Operating temp: 10 °C to 50°C.

Clamp-On CT Specification

Transformer ratio (Arms): 600A/300mA, 5A/2mA (Single Range); 1A, 5A, 300mA (Triple Range)
For CTR 600A/300mA,
Weight :
0.36 kg.
Dimension : overall 183(L) X 96(W) X 60 (D) mm
Conductor size : 96 mm
Burden Resistance : ≤ 2 ohms.
Accuracy : Class 0.5
Frequency Range : 50 to 400 Hz.

Back to top