Trinity

Home / Products / Digital Power / Multifunction meters / NF29

Back

NF29

 

The unit is low cost, easy-to-use, individual and multifunctional that enables to measure all the basic parameters required in an electrical installation and monitors electricity over and above basic metering. The entire range is very rugged and cost-effective. All these products are field proven and more than 100,000 units are active in service.


Multifunction Meters Product Catalog
( VAF| Orion | Entity+ | Empower | Tiny Pro | Boss | NF29 )



  • Features
  • Specifications

Main Features:

  • Micro-controller based
  • Measurement of all important Electrical Parameters
  • All parameters with default accuracy class 1.0S
  • Displays with customized LCD
  • Individual voltages and currents for all three phases (R-Y-B)
  • Individual three powers-KW, KVA and KVAR
  • Individual PF and system PF with lead (-) and lag side
  • Frequency (Hz), three energies (KWh, KVAh, KVARh)

Parameter Displays:

V, A, KWH, KVAH, KVARH, PF, Hz, System & Phase wise KW; KVA; KVAR.

SR.No.

Parameters
&
Option

Statistics
01
Volts R-N Direct Voltage Input : 20 to 300V L-N
Burden : 0.5VA
02
Volts Y-N
03
Volts B-N
04
Volts RY  Direct Voltage Input : Up to 500V L-L
Burden : 0.5VA
05
Volts YB
06
Volts BR
07
I R  Secondary Current Input : 5A or 1A (To be specified at the time of Ordering)
CT Primary : Site Selectable
Range of Reading : 5 – 5000A
Burden : < 1.0VA
Overload(Through CT) : 5A CT = 6A RMS Continuous
1A CT = 1.2A RMS Continuous
(Whole Current) : 120% of Imax continuous.
08
I Y
09
I B
10
Frequency 45 to 55 Hz, Accuracy : 0.3% of Reading
11
KWh Range of Reading : 0 to 9999999.9 KWh
Accuracy : 1.0S as per IS13779.
12
KVARh Range of Reading : 0 to 9999999.9 KVARh
Accuracy : 1.5% of Reading
(Between 0.5 Lag to 0.8 Lead
13
KVAh Range of Reading : 0 to 9999999.9 KVAh
Accuracy : 1.0% of Reading
14
System PF Accuracy : 1% of Reading (IPFI>0.5)
Range of Reading : 0.05 to 1.00 Lag/Lead
15
System KVA Accuracy : 1.0% of Reading
16
System KW Accuracy : 1.0% of Reading
17
System KVAR Accuracy : 1.5% of Reading
(Between 0.5 Lag to 0.8 Lead)
18
DISPLAY Customized LCD
19
Bezel 96x96 mm DIN enclosure
20
Depth 55 mm

Back to top
Home | About us | Products | Career with us | Partner with us | News | Contacts | Clientele | Disclaimer | Sitemap
Copyright © 2005 - 2008 Trinity Energy Systems Pvt. Ltd., Powered by: Megh Technologies